Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM04111
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/22/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/21/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
05/15/2008 | ELECTRIC - FINAL | Denied | 125 AMP 1/0 ALU. 150 AMP 2/0 LLU UNIT #2 1. SERVICE PANEL PLAN CALLS FOR 150 AMP MAINS 125 AMP INSTALLED WIRE, FEEDER STRANDS CUT TO FIT INTO BREAKER CONNECTION, PANEL LABEL REQUIRES TYPES OF BREAKER ACCEPTABLE, CUTLER HAMMER ISN'T ONE LISTED ON LABEL VERIFY SIZE OF SUB-PANEL FEEDER 2. EXT. AC UNITS MAX 30 AMP. FUSES 35's INSTALLED 3. #14 WIRE PROTECTED BY 20 AMP ARC FAULT BREAKER BEDROOMS 4. BOTH BEDROOMS ON 1 ARC FAULT, PANEL LABELED INCORRECTLY 5. LABEL FOR FURNACE TO BE DONE BY INSTALLER 6. OUTDOOR LIGHTING SCHEDULE WHAT IS FCO? UNIT #1 1. COUNTER TOP RECEPT MALFUNCTION TEST SOME OF SAME ITEMS FROM OTHER UNIT ABOVE |