Permit: T07CM04111

Parcel: 14025079E

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T07CM04111

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/22/2008 BUILDING - FINAL Approved IVRS - Inspection :*
05/21/2008 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) LAST INSPECTION, SUB PANEL FEEDERS, STRANDS WERE OUT TO FIT INTO BREAKERS, WRONG TYPE WERE INSTALLED, ? CORRECT BRAND INSTALLED, NOX COVERING ENTIRE CONNECTION
2) PLAN CALLS FOR FULL CUT OFF EXT. LIGHT FIXTURES, 6 TOTAL, TWO ARE NOT F.C.B
3) FURNACE READ LABEL, FIELD INSTALLER TO SUPPLY INFORMATION AS TO OVER CURRENT PROTECTION AND CIRCUIT AMPACITY ON THAT LABEL FOR BOTH UNITS
05/15/2008 BUILDING - FINAL Denied