Permit: T07CM04111

Parcel: 14025079E

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T07CM04111

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
03/21/2008 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
03/20/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
COMPLY WITH DETAIL B-B/5-3
2X6 STUDS @ 24" OC TO ROOF SHEATING
STAGGERED
03/17/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEM #5 ON FIREWALL NOT MET
2) MISSING H2.5 UNIT #1
03/12/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED APPROVED COPY OF TRUSS DRAWING
2) JOIST HANGERS MISSING AT ALL HIP JACKS
3) APPROVAL REQUIRED ON HEADERS AND CONNECTION AT GIRDER TRUSSES OVER DOORS
4) PROTECT ALL PLUMBING CLOSER THAN 1 1/2" TO FACE OF STUDS
5) SEE NOTE 4 PAGE A-1 AND COMPLY
6) NO ROOF ACCESS LADDER SHALL BE SECURED AND EXTEND 30" ABOVE ROOF