Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T07CM04109

Parcel: 140420200

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
03/19/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
MECHANICAL OK FOR TILES
02/21/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
PROVIDE SUPPORT ON FLEX DUCT NOT TO EXCEED 5' SUPPORT FROM STRUCTURE OK TO ROCK RESTROOMS