Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T07CM04109

Parcel: 140420200

Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Permit Number - T07CM04109

Inspection Description - ELECTRIC - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
04/25/2008 ELECTRIC - PROGRESS Approved
04/09/2008 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
OK 2" PVC FOR SUMP PUMP AT DOCK
03/26/2008 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) RELEASE OF POWER SUBJECT TO BOND POSTING
03/24/2008 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
OK PANELS HYDH, HYDL
OK BONDING & GROUNDING LOAD SIDE OF SERVICE
GROUND WIRE ON LINE SIDE FOR BONDING MUST BE 2/0 SIZED PER 250.66