Permit: T07CM04107

Parcel: 115061460


Addresses:

234 W PLATA ST


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T07CM04107

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/14/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
01/17/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PLUMBING INTERMEDIATE OK WITH EXCEPTION:
DELETION OF P-7 WILL REQUIRE STAMPED LETTER FROM ARCHITECT/ENGINEER
2. OK TO COVER WALLS SUBJECT TO LETTER
3. FLANGES OK
4. DEMO ON EXISTING TOILET ROOM OK
01/15/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. RE-READ PLUMBING PLAN NOTE NUMBER 6
2. VENT PIPING SHALL BE INSTALLED LEVEL OR SO DESIGNED AS TO DRAIN BACK TO THE FIXTURE SERVED
3. SEE CORRECTION NUMBER THREE FROM 12/31/07 CONTRACTOR TO PAY REINSPECTION FEE.
01/11/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
12/31/2007 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NOT INSTALLED PER PLAN. NO REDLINES ON SITE.
2. TRAP ARMS MAY NOT CHANGE SIZE
- TRAP AND TRAP ARM TO BE THE SAME SIZE
- TRAP MAY BE ONLY ONE SIZE LARGER THAN THE TAILPIECE TO WHICH IT IS CONNECTED.
3. CAP OFF ALL OPEN SEWER PIPES ASAP
4. SUPPORT ALL STUB OUTS
USE APPROVED SUPPORTS
SEE PLAN NOTE NUMBER 6
PLAN CALLS FOR TYPE "L" COPPER
FLANGE TO BE APPROVED TYPE

INSPECTION STOPPED - CONTINUED "NOT READY" WILL RESULT IN A REINSPECTION FEE.
12/21/2007 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL ALL PIPING PER APPROVED PLANS
2) PROVIDE APPROVAL SUPPORT ON ALL PIPING
3) PROVIDE TEST ON ALL PIPING