Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - PRE SLAB
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2007 | PLUMBING - PRE SLAB | Approved | IVRS - Inspection :* 1. BLAKE TEE IS LISTED AS A VERTICAL SURFACE WALL CLEANOUT. USE A DIRECTED FITTING 2. IS-5 2006 UPC - NO FEMALE ABS THREAD IN AN ACCESSIBLE LOCATION 3. N/H BAND LISTED FOR CAST IRON USE APPROVED MISSION COUPLING. REINSPECTED 2:20 PM CORRECTIONS MADE OK OK TO COVER UNDERGROUND DON'T FORGET TO WRAP PRE-POUR |