Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM04107
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/12/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/05/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PANEL DIRECTORIES TO BE CORRECT 2. AT MEZZANINE - IDENTIFY DISCONNECTS, STRAP FLEX WITHIN 12" OF TERMINATIONS, FC3 DISCONNECT TO HAVE PROPER FRONT WORKING CLEARANCE, WATER HEATER NOT IN 3. EXTERIOR - IDENTIFY DISCONNECTS WITH LABEL SUITABLE FOR ENVIRONMENT, PROPERLY TERMINATE ALL CONDUCTOR STRANDS UNDER LUG. |