Permit: T07CM04101

Parcel: 11310026B

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T07CM04101

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/15/2008 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
OK TO RELOCATE LIGHTS AGAINST WALL TO ALLOW ACCESS FAN COILS.
WILL CHECK CONDENSATE DRAINS ON FINAL
OK FOR CEILING TILES
02/13/2008 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
- JOINED CONDENSATE TO INCREASE IN SIZE TO 1"
- CONDENSATE TO BE INSULATED
- PROVIDE SECONDARY DRAINS
- PROVIDE FILTER ACCESS
- COVER COMBUSTIBLES IN PLENUMS
- PROVIDE PROPER STRAPS AND SUPPORTS
- PROVIDE DAMPERS ON OUTSIDE AIR
- INSULATE NON-LINED DUCT ABOVE CEILING, SUPPLY & RETURN DUCT IN PLENUMS NOT REQUIRED.