Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM04101
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/19/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1. SECURE RACEWAYS ON ROOF - NEC 110.13(B) 2. SEAL/CLOSE OFF END OF OLD FEEDER RACEWAY - NEC 110.12 (A) 3. MAKE CEILING J-BOX ACCESSIBLE (FEEDER CONDUIT BLOCKING) - NEC 110 |
|
| 03/18/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PANEL DIRECTORY NOT CORRECT 2. SERVICE TO BE OPEN & CEILING NEXT UNIT 3. PROVIDE ROOF ACCESS |
|
| 02/27/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION 1. H.P'S TO BE FED FROM PANEL PER PLAN 2. EQUIPMENT GROUNDS #6 AND SMALLER TO BE GREEN ENTIRE LENGTH 3. PANEL DIRECTORY NOT CORRECT 4. OFFICE FURNITURE NOT IN 5. SERVICE TO BE OPEN FOR INSPECTION 6. STILL NEED ROOF INSPECTION |