Permit: T07CM04101

Parcel: 11310026B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM04101

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/19/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
1. SECURE RACEWAYS ON ROOF - NEC 110.13(B)
2. SEAL/CLOSE OFF END OF OLD FEEDER RACEWAY -
NEC 110.12 (A)
3. MAKE CEILING J-BOX ACCESSIBLE (FEEDER CONDUIT BLOCKING) - NEC 110
03/18/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PANEL DIRECTORY NOT CORRECT
2. SERVICE TO BE OPEN & CEILING NEXT UNIT
3. PROVIDE ROOF ACCESS
02/27/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION
1. H.P'S TO BE FED FROM PANEL PER PLAN
2. EQUIPMENT GROUNDS #6 AND SMALLER TO BE GREEN ENTIRE LENGTH
3. PANEL DIRECTORY NOT CORRECT
4. OFFICE FURNITURE NOT IN
5. SERVICE TO BE OPEN FOR INSPECTION
6. STILL NEED ROOF INSPECTION