Inspection Status: Approved
Inspection History: PLUMBING - PROGRESS
Permit Number - T07CM04095
Inspection Description - PLUMBING - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/18/2008 | PLUMBING - PROGRESS | Approved | IVRS - Inspection :* CLOSET FLANGES LOOK GOOD |
|
03/14/2008 | PLUMBING - PROGRESS | Not ready for Inspection | COMPLY WITH PAST INSPECTION HISTORY | |
03/11/2008 | PLUMBING - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* CLOSET FLANGE INSTALLATION IS IN VIOLATION OF 2006 UPC INSTALLATION STANDARDS, REQUIRING FLANGE TO REST ON A FIRM BASE WITH THE TOP SURFACE 1/4" ABOVE FINISHED FLOOR. - ALSO, FLANGE INSTALLED IS A 3" CLOSET FLANGE, AND NOT DESIGNED TO GLUE INSIDE A 4" PIPE - YOU HAVE NOT PROVIDED A UPC LISTING. - MANUFACTURE PAPERWORK DOES NOT SPECIFY A 4" INSTALLATION. - FLANGE PROVIDED FOR COMPARISON HAS A RAISED CIRCLE ON THE OUTSIDE OF THE 3" HUB. - CONTRACTOR SHALL PAY A REINSPECTION FEE FOR FAILING TO COMPLY WITH THE CORRECTIONS FROM 1/25/08 |
|
03/05/2008 | PLUMBING - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* PLUMBER SHALL KEEP DRAINS PLUGGED, TAPE MAY NOT KEEP SEWER GAS OUT OF BUILDING NONE OF THE PREVIOUSLY NOTED CORRECTIONS HAVE BEEN COMPLETED. CONTINUED "DENIED" INSPECTIONS WILL RESULT IN REINSPECTION FEES. |