Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T07CM04081
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/19/2008 | FIRE - FINAL | Approved | ||
04/17/2008 | FIRE - FINAL | Partial Approval | STILL NEED TO REPAIR PROBLEMS UNDER SPRINKLER FINAL. | |
04/01/2008 | FIRE - FINAL | Partial Approval | 1. Temp C of O OK 2. Replace all missing escutcheons to sprinklers under canopy outside. 3. Add sprinkler coverage to room in storage area and check sprinkler coverage in storage area. 4. Correct sprinkler coverage in storage area north. 5. Replace painted sprinkler head in storage area north. |
|
03/24/2008 | FIRE - FINAL | Not ready for Inspection | 1.) Need up to date fire sprinkler inspection last report on file 10/21/2005. 2.) Need up to 5 year alarm check valve inspection done. 3.) Need to replace all missing ceciling tiles. 4.) Fire inspector needs to make entry into building to check sprinkler coverage. 5.) Need set of approved floor plans and site plans on site when calling in for inspection. |