Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T07CM04081
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/19/2008 | FIRE SPKLR - FINAL | Approved | ||
04/17/2008 | FIRE SPKLR - FINAL | Denied | REPLACE ALL MISSING ESCUTCHEONS TO SPRINKLERS UDER FRONT CANOPY. REPAIR OR REPLACE FIRE ALARM CHECK VALVE LEAKING. |
|
04/17/2008 | FIRE SPKLR - FINAL | Partial Approval | Replace all missing escutcheons to sprinklers under canopy outside. REPAIR OR REPLACE FIRE ALARM CHECK VALVE TESTING SHOWED IT FAILED |
|
04/03/2008 | FIRE SPKLR - FINAL | Partial Approval | Temp C of O OK 2. Replace all missing escutcheons to sprinklers under canopy outside. 3. Add sprinkler coverage to room in storage area and check sprinkler coverage in storage area. 4. Correct sprinkler coverage in storage area north. 5. Replace painted sprinkler head in storage area north. |
|
03/24/2008 | FIRE SPKLR - FINAL | Denied | 1.) Need up to date fire sprinkler inspection last report on file 10/21/2005. 2.) Need up to 5 year alarm check valve inspection done. 3.) Need to replace all missing ceciling tiles. 4.) Fire inspector needs to make entry into building to check sprinkler coverage. 5.) Need set of approved floor plans and site plans on site when calling in for inspection. |