Permit: T07CM04081

Parcel: 11205060C

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T07CM04081

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/19/2008 FIRE SPKLR - FINAL Approved
04/17/2008 FIRE SPKLR - FINAL Denied REPLACE ALL MISSING ESCUTCHEONS TO SPRINKLERS UDER FRONT CANOPY.
REPAIR OR REPLACE FIRE ALARM CHECK VALVE LEAKING.
04/17/2008 FIRE SPKLR - FINAL Partial Approval Replace all missing escutcheons to sprinklers under canopy outside.
REPAIR OR REPLACE FIRE ALARM CHECK VALVE TESTING SHOWED IT FAILED
04/03/2008 FIRE SPKLR - FINAL Partial Approval Temp C of O OK
2. Replace all missing escutcheons to sprinklers under canopy outside.
3. Add sprinkler coverage to room in storage area and check sprinkler coverage in storage area.
4. Correct sprinkler coverage in storage area north.
5. Replace painted sprinkler head in storage area north.
03/24/2008 FIRE SPKLR - FINAL Denied 1.) Need up to date fire sprinkler inspection last report on file 10/21/2005.
2.) Need up to 5 year alarm check valve inspection done.
3.) Need to replace all missing ceciling tiles.
4.) Fire inspector needs to make entry into building to check sprinkler coverage.
5.) Need set of approved floor plans and site plans on site when calling in for inspection.