Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T07CM04081
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/06/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR CEILING TILES ON FINAL PROVIDE AUDIBLE & VISIBLE ALARMS FOR DUCT SMOKE DETECTORS. PRETEST BEFORE FINAL INSPECTION |
|
02/27/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROVIDE SECONDARY DRAIN - SECONDARY DRAIN PAN CANNOT DUMP ON FLOOR - DUCT SMOKE DETECTORS NOT PROPERLY INSTALLED - VERIFY P-TRAPS HAVE PROPER FALL - PROVIDE FILTRATION FOR OUTSIDE AIR |
|
01/28/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |