Permit: T07CM04081

Parcel: 11205060C

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T07CM04081

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
03/06/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK FOR CEILING TILES
ON FINAL PROVIDE AUDIBLE & VISIBLE ALARMS FOR DUCT SMOKE DETECTORS. PRETEST BEFORE FINAL INSPECTION
02/27/2008 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PROVIDE SECONDARY DRAIN
- SECONDARY DRAIN PAN CANNOT DUMP ON FLOOR
- DUCT SMOKE DETECTORS NOT PROPERLY INSTALLED
- VERIFY P-TRAPS HAVE PROPER FALL
- PROVIDE FILTRATION FOR OUTSIDE AIR
01/28/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*