Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/06/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR CEILING TILES ON FINAL PROVIDE AUDIBLE & VISIBLE ALARMS FOR DUCT SMOKE DETECTORS. PRETEST BEFORE FINAL INSPECTION |
|
| 02/27/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROVIDE SECONDARY DRAIN - SECONDARY DRAIN PAN CANNOT DUMP ON FLOOR - DUCT SMOKE DETECTORS NOT PROPERLY INSTALLED - VERIFY P-TRAPS HAVE PROPER FALL - PROVIDE FILTRATION FOR OUTSIDE AIR |
|
| 01/28/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |