Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM04081
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/04/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/03/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PLANS CALL FOR REPLACEMENT OF 2/0 WITH 3/0 FOR "AA" PANEL/DISCONNECT 2. BOND "HB" RISER AND NIPPLE - NEC 250.92 3. REMOVE "HB" OLD SERVICE CONDUCTORS FROM GUTTER AND FEED FROM NEW METER BASE 4. NEW NEUTRAL FOR DISCONNECT TO BOND TO ENCLOSURE - 250.24C 5. IDENTIFY CONDUCTORS FOR AC UNITS 6. MULTIPLE GROUNDS NOT ALLOWED UNDER LUG DISC. HP4 7. EMERGENCY TO BE WORKING/PER PLAN/PER NEC 700.12F 8. PROVIDE OVERCURRENT PROTECTION FOR TRANSFORMER NEC 240.21C 9. GEC FOR TRANSFORMER TO BE UNDER SMAE TERMINATION AS BONDING JUMPER - NEC 250.303 PARTIAL INSPECTION |
|
04/01/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CALL WHEN ALL WORK COMPLETE, PER PLAN, AND PER CODE NO INSPECTION AT THIS TIME EQUIPMENT TO BE OPEN FOR INSPECTION |