Permit: T07CM04081

Parcel: 11205060C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM04081

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/04/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/03/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. PLANS CALL FOR REPLACEMENT OF 2/0 WITH 3/0 FOR "AA" PANEL/DISCONNECT
2. BOND "HB" RISER AND NIPPLE - NEC 250.92
3. REMOVE "HB" OLD SERVICE CONDUCTORS FROM GUTTER AND FEED FROM NEW METER BASE
4. NEW NEUTRAL FOR DISCONNECT TO BOND TO
ENCLOSURE - 250.24C
5. IDENTIFY CONDUCTORS FOR AC UNITS
6. MULTIPLE GROUNDS NOT ALLOWED UNDER LUG DISC. HP4
7. EMERGENCY TO BE WORKING/PER PLAN/PER NEC 700.12F
8. PROVIDE OVERCURRENT PROTECTION FOR TRANSFORMER
NEC 240.21C
9. GEC FOR TRANSFORMER TO BE UNDER SMAE TERMINATION AS BONDING JUMPER - NEC 250.303

PARTIAL INSPECTION
04/01/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CALL WHEN ALL WORK COMPLETE, PER PLAN, AND PER CODE
NO INSPECTION AT THIS TIME
EQUIPMENT TO BE OPEN FOR INSPECTION