Permit: T07CM04076

Parcel: 122060080

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/03/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/01/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED TO UNBUNDLE ROMEX AT MAIN PANEL HOME RUNS ALLOWED 24" BUNDLING ONLY
2) NEED TO RECHECK HOMERUNS STAPLED BY LATH
3) NEED 24" SEPERATION AT WALL BOXES AT FIRE WALL OR USE APPROVED PUTTY PACKS
4) NEED FIRE RATED BOXES AT FIREWALL (NO MUD RINGS ALLOWED)