Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/03/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/01/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO UNBUNDLE ROMEX AT MAIN PANEL HOME RUNS ALLOWED 24" BUNDLING ONLY 2) NEED TO RECHECK HOMERUNS STAPLED BY LATH 3) NEED 24" SEPERATION AT WALL BOXES AT FIRE WALL OR USE APPROVED PUTTY PACKS 4) NEED FIRE RATED BOXES AT FIREWALL (NO MUD RINGS ALLOWED) |