Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T07CM04066

Parcel: 12410008C


Addresses:

999 E 16TH ST

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
11/27/2007 FIRE - FINAL Approved
11/14/2007 FIRE - FINAL Denied 1. SUPPLY ROOM NEEDS SPRINKLER COVERAGE OR REMOVE ROOF AND KEEP OPEN TO THE UPRIGHT SPRINKLER COVERAGE.
2. NEED UP TO DATE FIRE SPRINKLER INSPECTION LAST REPORT ON FILE FEB. 2003. INSPECTIONS SHALL BE DONE ONCE A YEAR.
3. REPAIR WIRING TO FIRE ALARM BELL ON SPRINKLER SYSTEM, THIS A DEDICATED CIRCUIT AND IS TO BE USE ONLY FOR THE SPRINKLER ALARM BELL.
4. FIRE HOSE SHALL BE TESTED
5. REMOVE WIRNG TO OUTLET OR ADD A COVER PLATE TO 4 SQUARE BOX ON NORTH WALL BY COOLER (INSIDE).
6. NEED TO ADD ADDRESS NUMBERS ON BUILDING.