Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T07CM04066
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/27/2007 | FIRE - FINAL | Approved | ||
| 11/14/2007 | FIRE - FINAL | Denied | 1. SUPPLY ROOM NEEDS SPRINKLER COVERAGE OR REMOVE ROOF AND KEEP OPEN TO THE UPRIGHT SPRINKLER COVERAGE. 2. NEED UP TO DATE FIRE SPRINKLER INSPECTION LAST REPORT ON FILE FEB. 2003. INSPECTIONS SHALL BE DONE ONCE A YEAR. 3. REPAIR WIRING TO FIRE ALARM BELL ON SPRINKLER SYSTEM, THIS A DEDICATED CIRCUIT AND IS TO BE USE ONLY FOR THE SPRINKLER ALARM BELL. 4. FIRE HOSE SHALL BE TESTED 5. REMOVE WIRNG TO OUTLET OR ADD A COVER PLATE TO 4 SQUARE BOX ON NORTH WALL BY COOLER (INSIDE). 6. NEED TO ADD ADDRESS NUMBERS ON BUILDING. |