Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T07CM04065

Parcel: 12701002C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM04065

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/03/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/31/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
12/27/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
12/24/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
12/20/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. CONDUCTOR COLORS TO BE AS PER 210.5(C) AMENDMENTS
2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE - 314.20
3. MISSING COVER PLATE
4. PANEL DIRECTORIES NOT LEGIBLE - 408.4
5. FINISH VDV CABLING 725.3, 800.3, 300.11
6. NEED TO SEE CONNECTIONS OF OFFICE FURNITURE TO VERIFY 605.7

RECEIVED LETTER FOR EMERGENCY SYSTEM