Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM04065
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/31/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 12/27/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 12/24/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 12/20/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. CONDUCTOR COLORS TO BE AS PER 210.5(C) AMENDMENTS 2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE - 314.20 3. MISSING COVER PLATE 4. PANEL DIRECTORIES NOT LEGIBLE - 408.4 5. FINISH VDV CABLING 725.3, 800.3, 300.11 6. NEED TO SEE CONNECTIONS OF OFFICE FURNITURE TO VERIFY 605.7 RECEIVED LETTER FOR EMERGENCY SYSTEM |