Permit: T07CM04065

Parcel: 12701002C

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM04065

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/03/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
12/31/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. INSTALL RECEPTACLE MODULES OR CAP ON OFFICE FURNITURE
2. FINISH PREVIOUS INSPECTION #6 12/20/07
12/27/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
12/24/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) NO ABREVEATIONS FOR PANEL SCHEDULES 408.4
2) NEED TO SEE OFFICE FURNITURE CONNECTIONS
3) TAPE TO ENCIRCLE CONDUCTORS
12/20/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
12/17/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. FINISH FILLING OPEN CONDUIT
2. FILL UNUSED OPENING IN JUNCTION BOX

OK TO TILE EXCEPT AS NOTED - CHECK ON FINAL
12/14/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 2X4, 2X2 AND EXIT LIGHTS & CANS

1. FINISH VDV CABLING PER 725.3 & 6, 800.3 & 24, 300.11
2. SEAL OPEN CONDUITS EXITING SPACE

1. REMOVE TILE TO INSPECT - AROUND FIXTURES, JUNCTION BOXES AND CABLING
2. SUPPORT VDV CABLING PER 725.3 & 6, 800.3 & 24, 300.11
12/13/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
*REVISE PLANS FOR EM & EXIT LIGHTS
12/07/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
CLOSE UP OR REMOVE FAN ABOVE CEILING
OK TILE ROOM 115 ONLY
11/02/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS
11/01/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PROTECT MC CABLE AT TOP PLATES, AT STUDS
2. NEED TO SEE CABLING FOR IN WALLS

*VDV CABLING TO BE AS PER 725.3 & 6, 800.3 & 6, 300.11