Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM04063
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/07/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
12/26/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SURFACE EQUIPMENT WILL BE CHECKED ON FINAL 2) OK WALL AND HARD LID COVER HALLWAY (NEW SWITCH AND RELOCATED LIGHT) |
|
12/14/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CALL IN FOR REINSPECTION TO SEE TERMINATIONS AT DISCONNECTS (SERVICE) |
|
12/13/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. BURNDY T-SPLICES WILL GROUND DISCONNECT (EXISTING) PLANS SHOW J-BOX OR REPLACE LUGS IN EXISTING DISCONNECTS WITH DUAL CONDUCTOR RATING OR OTHER - MAIN BONDING JUMPER REQUIRED IN SERVICE DISCONNECTS - HAVE ARCH ADDRESS DRAIN HEATER FOR WALK IN COOLERS - POWER CONDUCTORS ENTERING CONDENSORS SHOULD BE IN RACEWAY OR USE POWER CONTROL CABINET SECTION TO ENTER - LIGHTING IS BY OTHER CONTR. (JB ELECT) |