Permit: T07CM04063

Parcel: 12906523A


Addresses:

3031 E 22ND ST


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM04063

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/07/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
12/26/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SURFACE EQUIPMENT WILL BE CHECKED ON FINAL
2) OK WALL AND HARD LID COVER HALLWAY (NEW SWITCH AND RELOCATED LIGHT)
12/14/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
CALL IN FOR REINSPECTION TO SEE TERMINATIONS AT DISCONNECTS (SERVICE)
12/13/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. BURNDY T-SPLICES WILL GROUND DISCONNECT (EXISTING)
PLANS SHOW J-BOX OR REPLACE LUGS IN EXISTING DISCONNECTS WITH DUAL CONDUCTOR RATING OR OTHER
- MAIN BONDING JUMPER REQUIRED IN SERVICE DISCONNECTS
- HAVE ARCH ADDRESS DRAIN HEATER FOR WALK IN COOLERS
- POWER CONDUCTORS ENTERING CONDENSORS SHOULD BE IN RACEWAY OR USE POWER CONTROL CABINET SECTION TO ENTER
- LIGHTING IS BY OTHER CONTR. (JB ELECT)