Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07CM04061
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/19/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
08/06/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) TESTED DUCT SMOKE DETECTORS AND FIRE DAMPERS 2) NEED TO SEE DUCT REPLACEMENT ON ROOF 3) EVERYTHING ELSE OK |
|
08/05/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. FIRE/SMOKE DAMPERS ARE WORKING PROPERLY 2. DUCT SMOKE DETECTORS NOT SETTING OFF AUDIBLE AND VISIBLE SIGNAL 3. FAN IS SHUTTING DOWN 4. PROVIDE R8 DUCT INSULATION IN EXPOSED DUCT ON ROOF AIR BALANCE OK |
|
08/01/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. FOR TEMP FINAL ALL FIRE DAMPERS & DUCT SMOKE DETECTORS WILL NEED TO BE TESTED 2. PROVIDE LETTER FROM ENGINEER IF CHANGING DUCT INSULATION REQUIREMENTS |