Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T07CM04061

Parcel: 11207461C


Addresses:

2901 E GRANT RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T07CM04061

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/28/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK FOR CEILING TILES
ON FINAL PROVIDE AIR BALANCE REPORT, ACCESS TO ROOF, PROVIDE R-8 INSULATION IN ALL EXPOSED DUCT ON ROOF AS PER PLANS AND CODE. RELIEF HOODS REQUIRE DAMPERS.
07/24/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. PROVIDE ANGLE IRON AROUND ALL FIRE & SMOKE DAMPERS
2. PROVIDE ACCESS DOORS FOR ALL DAMPERS
3. PROVIDE A DUCT SMOKE DETECTOR FOR ALL FIRE/SMOKE DAMPERS AS PER 607.3.2.1 IMC
4. PROVIDE INSTALL INSTRUCTIONS FOR DAMPERS
5. ANGLE IRON NOT INSTALLED CORRECTLY
6. DAMPER IN WATER TREATMENT ROOM HAS NO FRAMING
07/18/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
PROVIDE MANUF. SPECS ON LINEAR DIFFUSERS IN REGARDS TO INSULATION R-VALUE MUST BE MIN. R-4.2

ALL LIFT SAFETY DEVICES MUST BE INSTALLED COMPLETE AND OPERATIONAL PRIOR TO ANY T.C.O REQUEST