Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T07CM04061
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/28/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR CEILING TILES ON FINAL PROVIDE AIR BALANCE REPORT, ACCESS TO ROOF, PROVIDE R-8 INSULATION IN ALL EXPOSED DUCT ON ROOF AS PER PLANS AND CODE. RELIEF HOODS REQUIRE DAMPERS. |
|
07/24/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. PROVIDE ANGLE IRON AROUND ALL FIRE & SMOKE DAMPERS 2. PROVIDE ACCESS DOORS FOR ALL DAMPERS 3. PROVIDE A DUCT SMOKE DETECTOR FOR ALL FIRE/SMOKE DAMPERS AS PER 607.3.2.1 IMC 4. PROVIDE INSTALL INSTRUCTIONS FOR DAMPERS 5. ANGLE IRON NOT INSTALLED CORRECTLY 6. DAMPER IN WATER TREATMENT ROOM HAS NO FRAMING |
|