Permit: T07CM04061

Parcel: 11207461C


Addresses:

2901 E GRANT RD


Inspection Status: Approved

Inspection History: PLUMBING - ABOVE CEILING

Permit Number - T07CM04061

Inspection Description - PLUMBING - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/18/2008 PLUMBING - ABOVE CEILING Approved IVRS - Inspection :*
1. CALL 03035 FOR CLOSET FLANGE INSPECTION
2. CALL 03035 FOR YARD WATER PIPING
NOTE: ALL YARDWATER PIPING TO BE INSTALLED A
MINIMUM 12" DEEP

TRACER TO BE CONTINUOUS
07/17/2008 PLUMBING - ABOVE CEILING Not ready for Inspection PVC SHALL BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION, AND AT THE END OF BRANCHES; THEN NO MORE THAN FOUR FEET BETWEEN HANGERS

NOTE: INDIRECT WASTE PIPING MAY NOT BE COMBINED