Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM04061
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/20/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* WAITING ON FIELD EVAL. PAPER WORK |
|
08/07/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK ROOF 2) NEED NRTL LISTING-NOT SELF CERTIFICATIONS |
|
08/05/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ROOF: 1. PROTECT CONDUCTOR AT FITTING 300.4 2. MAINTAIN WORKING CLEARANCE AT A/C UNIT DISCONNECT 3. SUPPORT SEAL TITE BUILDING: 1. VERIFYING EQUIPMENT |
|
08/01/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" - 314.20 2. PLEASE VERIFY LISTING OF SCALE, BIO CARB, BI CARB 3. FINISH DISCONNECT LABELING 4. LABEL PANEL DIRECTORIES - 408.4 |