Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/20/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 07/30/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. FINISH VDV CABLING OK TO TILE - CHECK ON FINAL |
|
| 07/29/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. ATTACH FIXTURES TO GRID - 410.16 2. ELECTRICAL TO BE SUPPORTED BOTH ENDS - 300.11 3. VDV CABLING TO BE SUPPORTED 725.24, 800.24, 300.11 4. NEED SUPPORT WIRES FOR EXIT SIGNS 5. SUPPORT M/C CABLE 12" FROM BOXES |
|
| 07/24/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* DO NOT CALL FOR INSPECTION UNTIL ELECTRICAL CONTRACTOR READY. NEXT INSPECTION THAT IS NOT READY WILL RESULT IN REINSPECTION FEE. |