Permit: T07CM04041

Parcel: 11016223A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM04041

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/01/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/29/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOXES MORE THAN 1/4" -- 314.20
2. VERIFY CORD & PLUG FOR AUTOMATIC DOOR & USE CORD STRAIN RELIEF
3. INSTALL DEVICES SECURE TO WALLS
4. EXIT SIGNS TO BE AS PER 700.12 - ALSO, ONE SIGN NOT WORKING
5. BOND DEVICE NEEDED PER 250.97
6. TIGHTEN LOOSE FITTINGS
7. LABEL PANEL PER 408.4 NO ABBREVIATIONS
8. MAKE UP FIRE ALARM CONTROL PANEL
9. SUPPORT CONDUITS ABOVE PANEL WITHIN 3'
10. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM FLOOR BOXES - 110.12
11. MISSING MOTION SENSORS AS PER PLANS
12. PROTECT CONDUCTORS FROM SHARP METAL EDGES
13. SHEET METAL THREAD SCREWS NOT ALLOWED FOR GROUNDING AND GROUND FIXTURE AS PER MANUFACTURE REQUIREMENTS
14. WHERE IS BATTERY PACK FOR FIXTURE "D"
15. TRANSFORMER TO MAINTAIN 6" CLEARANCE TO WALL

* CHECK ROOF NEXT TIME