Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/01/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/29/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOXES MORE THAN 1/4" -- 314.20 2. VERIFY CORD & PLUG FOR AUTOMATIC DOOR & USE CORD STRAIN RELIEF 3. INSTALL DEVICES SECURE TO WALLS 4. EXIT SIGNS TO BE AS PER 700.12 - ALSO, ONE SIGN NOT WORKING 5. BOND DEVICE NEEDED PER 250.97 6. TIGHTEN LOOSE FITTINGS 7. LABEL PANEL PER 408.4 NO ABBREVIATIONS 8. MAKE UP FIRE ALARM CONTROL PANEL 9. SUPPORT CONDUITS ABOVE PANEL WITHIN 3' 10. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM FLOOR BOXES - 110.12 11. MISSING MOTION SENSORS AS PER PLANS 12. PROTECT CONDUCTORS FROM SHARP METAL EDGES 13. SHEET METAL THREAD SCREWS NOT ALLOWED FOR GROUNDING AND GROUND FIXTURE AS PER MANUFACTURE REQUIREMENTS 14. WHERE IS BATTERY PACK FOR FIXTURE "D" 15. TRANSFORMER TO MAINTAIN 6" CLEARANCE TO WALL * CHECK ROOF NEXT TIME |