Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T07CM04041

Parcel: 11016223A

Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Permit Number - T07CM04041

Inspection Description - ELECTRIC - TEMP POWER FOR TEST

Inspection Status - Approved

Date Description Inspector Results Comments
05/01/2008 ELECTRIC - TEMP POWER FOR TEST Approved IVRS - Inspection :*
04/22/2008 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
04/21/2008 ELECTRIC - TEMP POWER FOR TEST Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CONDUCTOR ID TAPE TO ENCIRCLE AS WE DISCUSSED
2. INSTALL REJECTION PINS AND FUSES
3. FINISH ITEMS 4,6 AND 8 OF PREVIOUS INSPECTION
4. PANEL COVERS TO BE MARKED AS PER 200.5
04/14/2008 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection :*
1. ONLY ONE CONDUCTOR PER TERMINAL
2. IDENTIFY ISOLATED GROUND WITH YELLOW MARKINGS
3. INSTALL IG GROUND BAR
4. VERIFY PATH OF GROUND FOR TRANSFORMER
5. SECURE TRANSFORMER TO FLOOR
6. VERIFY DERATING PER 310.15
7. REMOVE MAIN BOND SCREW
8. MAIN SERVICE TO BUILDING TO PASS INSPECTIONS PRIOR TO CLEARANCES