Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
Permit Number - T07CM04041
Inspection Description - ELECTRIC - TEMP POWER FOR TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/01/2008 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection :* | |
04/22/2008 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection :* | |
04/21/2008 | ELECTRIC - TEMP POWER FOR TEST | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CONDUCTOR ID TAPE TO ENCIRCLE AS WE DISCUSSED 2. INSTALL REJECTION PINS AND FUSES 3. FINISH ITEMS 4,6 AND 8 OF PREVIOUS INSPECTION 4. PANEL COVERS TO BE MARKED AS PER 200.5 |
|
04/14/2008 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection :* 1. ONLY ONE CONDUCTOR PER TERMINAL 2. IDENTIFY ISOLATED GROUND WITH YELLOW MARKINGS 3. INSTALL IG GROUND BAR 4. VERIFY PATH OF GROUND FOR TRANSFORMER 5. SECURE TRANSFORMER TO FLOOR 6. VERIFY DERATING PER 310.15 7. REMOVE MAIN BOND SCREW 8. MAIN SERVICE TO BUILDING TO PASS INSPECTIONS PRIOR TO CLEARANCES |