Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T07CM04040

Parcel: 13710507B


Addresses:

5650 S 12TH AV #180


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T07CM04040

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/08/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
03/28/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
DO NOT USE SEISMIC TO SUPPORT MC CABLE
THAT ARE INTENDED TO SUPPORT GRID
INSTALL YOUR OWN WIRES TO SUPPORT ELECTRICAL OR DATA
300.11 NEC

STEVE 331-0407
HART 240-9849
03/28/2008 ELECTRIC - ABOVE CEILING Partial Approval - REMOVE ABANDONED SECURITY CABLE
- SUPPORT MC CABLE FOR HOOD AT BOX TERMINATION

CONTR. REQUEST AFTER HRS. (SAT) INSP.
PAID CK#5057 $300.00 (JIM MILITELLO PICKED UP CHECK)