Permit: T07CM04027

Parcel: 10819013E


Addresses:

1090 E RIVER RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM04027

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/07/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
KENT @ 668-1498
01/25/2008 ELECTRIC - FINAL Cancelled IVRS - AP canceled
01/24/2008 ELECTRIC - FINAL Partial Approval WATER HEATER NOT TO BE CORD & PLUG
NEED DISCONNECTING MEANS
01/22/2008 ELECTRIC - FINAL Partial Approval
01/22/2008 ELECTRIC - FINAL Cancelled IVRS - AP canceled
12/17/2007 ELECTRIC - FINAL Partial Approval
12/10/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PREVIOUS CORRECTIONS STILL NOT COMPLETED -
A REINSPECTION FEE MUST BE PAID

1. EQUIPMENT GROUND TO BE GREEN - NEC 250.119
2. NEUTRAL TO BE WHITE - NEC 200.6
3. CONDUIT ENTRIES INTO J-BOXES TO BE SEALED - NEC 314.15
4. J-BOXES UNDERSIZED - NEED PROPER MINIMUM DISTANCE BETWEEN RACEWAYS - NEC 314.28 A2
5. REMOVE ALL PAINT UNDER GROUND LUGS - NEC 250.12
6. GROUND SCREWS FOR LUGS TO BE PROPERLY THREADED TAP HOLE SCREW CAN TIGHTEN DOWN
7. PROVIDE ACCESS TO GUEST HOUSE - DOES NOT APPEAR TO BE PROPERLY WIRED/HAVE BARE NEUTRAL? WHITE USED AS HOT?
8. NEED PROTECTIVE BUSHING #4 & LARGER WIRE - NEC 300
12/06/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CORRECTIONS NOT COMPLETED
ELECTRICIAN TO BE ON SITE
11/27/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*