Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* KENT @ 668-1498 |
|
| 01/25/2008 | ELECTRIC - FINAL | Cancelled | IVRS - AP canceled | |
| 01/24/2008 | ELECTRIC - FINAL | Partial Approval | WATER HEATER NOT TO BE CORD & PLUG NEED DISCONNECTING MEANS |
|
| 01/22/2008 | ELECTRIC - FINAL | Partial Approval | ||
| 01/22/2008 | ELECTRIC - FINAL | Cancelled | IVRS - AP canceled | |
| 12/17/2007 | ELECTRIC - FINAL | Partial Approval | ||
| 12/10/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PREVIOUS CORRECTIONS STILL NOT COMPLETED - A REINSPECTION FEE MUST BE PAID 1. EQUIPMENT GROUND TO BE GREEN - NEC 250.119 2. NEUTRAL TO BE WHITE - NEC 200.6 3. CONDUIT ENTRIES INTO J-BOXES TO BE SEALED - NEC 314.15 4. J-BOXES UNDERSIZED - NEED PROPER MINIMUM DISTANCE BETWEEN RACEWAYS - NEC 314.28 A2 5. REMOVE ALL PAINT UNDER GROUND LUGS - NEC 250.12 6. GROUND SCREWS FOR LUGS TO BE PROPERLY THREADED TAP HOLE SCREW CAN TIGHTEN DOWN 7. PROVIDE ACCESS TO GUEST HOUSE - DOES NOT APPEAR TO BE PROPERLY WIRED/HAVE BARE NEUTRAL? WHITE USED AS HOT? 8. NEED PROTECTIVE BUSHING #4 & LARGER WIRE - NEC 300 |
|
| 12/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CORRECTIONS NOT COMPLETED ELECTRICIAN TO BE ON SITE |
|
| 11/27/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |