Permit: T07CM04027

Parcel: 10819013E


Addresses:

1090 E RIVER RD


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T07CM04027

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
12/17/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
12/10/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
12/06/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/27/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING CONNECTION NEC 250.8
2) PAINT TO BE REMOVED UNDER GROUND LUGS NEC 250.12
3) INSULATED EQUIPMENT GROUND TO BE FREEN ENTIRE LENGTH NEC 250.119
4) SEALING TYPE LOCK NUTS REQUIRED FOR SIDE ENTRY INTO 3R WEATHER PROOF J-BOX NEC 314.15
5) J-BOX UNDERSIZED NEC 314.28 A 2
6) NEED EMT STRAP FOR EMT BETWEEN J-BOXES NEC 358.30A
7) SEAL UNUSED OPENINGS NEC 110.12 A
8) GROUND TOP J-BOX WITH PROPERLY SIZED EQUIPMENT GROUND NEC 250.122
9) CHECK WIRING TO GUEST HOUSE IN J-BOX. WHERE IS NEUTRAL ?
10) WIRING NOT PROPERLY IDENTIFIED ?
11) INSULATED NEUTRAL #6 AND SMALLER TO BE WHITE ENTIRE LENGTH NEC 200.6
12) PARTIAL INSPECTION-PROVIDE ELECTRICIANS PHONE NUMBER
11/05/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) NOTE: MARK LOCATION OF GROUND RODS FOR FINAL-I COULD NOT FIND