Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T07CM04027
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/17/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
12/10/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
12/06/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
11/27/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING CONNECTION NEC 250.8 2) PAINT TO BE REMOVED UNDER GROUND LUGS NEC 250.12 3) INSULATED EQUIPMENT GROUND TO BE FREEN ENTIRE LENGTH NEC 250.119 4) SEALING TYPE LOCK NUTS REQUIRED FOR SIDE ENTRY INTO 3R WEATHER PROOF J-BOX NEC 314.15 5) J-BOX UNDERSIZED NEC 314.28 A 2 6) NEED EMT STRAP FOR EMT BETWEEN J-BOXES NEC 358.30A 7) SEAL UNUSED OPENINGS NEC 110.12 A 8) GROUND TOP J-BOX WITH PROPERLY SIZED EQUIPMENT GROUND NEC 250.122 9) CHECK WIRING TO GUEST HOUSE IN J-BOX. WHERE IS NEUTRAL ? 10) WIRING NOT PROPERLY IDENTIFIED ? 11) INSULATED NEUTRAL #6 AND SMALLER TO BE WHITE ENTIRE LENGTH NEC 200.6 12) PARTIAL INSPECTION-PROVIDE ELECTRICIANS PHONE NUMBER |
|
11/05/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) NOTE: MARK LOCATION OF GROUND RODS FOR FINAL-I COULD NOT FIND |