Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/30/2008 PLUMBING - FINAL Approved PER LEERAY
05/27/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1. PROVIDE CORRECT CLEANOUT PLUG AT BR SINK SEAL PLUG
2. SECURE DW DRAIN HOSE
3. INSTALL MECHANICAL WATER HAMMER ARRESTORS
4. STILL NEED BAC T REPORT AND APPROVAL FOR LAVITORY
5. FIXTURE WATER TESTS OK
05/23/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
WORK NOT COMPLETE
ALSO; PROVIDE ENGINEER APPROVAL OF TOTO LAVATORIES
AND FAUCETS. PROVIDE COPIES OF WATER CERTIFICATIONS REQUIRED BY PLAN SPEC. #21
05/22/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OPEN FRONT TOILET SEATS
2) COMPLETE WORK, SEAL SINKS AND WATER TEST
3) DW REQUIRES WATER HAMMER ARRESTOR AND HIGH LOOP ON HOSE