Permit: T07CM04017

Parcel: 123153350


Addresses:

1011 E ELM ST


Inspection Status: Partial Approval

Inspection History: BUILDING - FINAL

Permit Number - T07CM04017

Inspection Description - BUILDING - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
11/10/2009 BUILDING - FINAL Partial Approval IVRS - Inspection :*
1) REMOVE WALL FRAMING AROUND WATER HEATER
2) DO NOT USE METAL TAPE FOR SUPPORT ON GAS LINE AND USE 2 HOLE STRAPS
3) INSULATE COPPER PIPE OUTSIDE OF BLDG
4) EXTERIOR ABS TO BE SUPPORTED 4' ON CENTER MAX AND PAINTED WITH LATEX PAINT
5) SEAL EXTERIOR WALL PENETRATIONS
6) FINISH ALL WORK
7) PERMANENT HEAT SOURCE REQUIRED FOR HABITABLE ROOMS
03/24/2008 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*