Inspection History: BUILDING - FINAL
Permit Number - T07CM04017
Inspection Description - BUILDING - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/10/2009 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1) REMOVE WALL FRAMING AROUND WATER HEATER 2) DO NOT USE METAL TAPE FOR SUPPORT ON GAS LINE AND USE 2 HOLE STRAPS 3) INSULATE COPPER PIPE OUTSIDE OF BLDG 4) EXTERIOR ABS TO BE SUPPORTED 4' ON CENTER MAX AND PAINTED WITH LATEX PAINT 5) SEAL EXTERIOR WALL PENETRATIONS 6) FINISH ALL WORK 7) PERMANENT HEAT SOURCE REQUIRED FOR HABITABLE ROOMS |
|
03/24/2008 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* |