Inspection History Details
Permit: T07CM04008
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/28/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK POLE LIGHTS-RECEIVED SPECIAL INSPECTION REPORT FOR LIGHTING COMPLIANCE 2) EXISTING PANEL IS CLASS CTL LIMITED TO 42 OVER CURRENT ? PANEL HAS APPROX 49 3) HAVE SPLIT BREAKERS IN POSITIONS IN PANEL NOT ALLOWED PER MANUFACTURE |
|
| 05/15/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. OK UNDERGROUND FOR POLE LIGHTS NORTH END OF LOT 2. OK 4 POLE BASES NORTH END OF LOT |