Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/11/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* OSA REPORT OK |
|
| 09/05/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. PROVIDE BALANCE REPORT ON O.S.A PER PLANS 2. PROVIDE A MEANS TO SECURE FILTER IN O.S.A ALL OTHER CORRECTIONS DATED 9/3/08 OK |
|
| 09/03/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 4' MAX. ON PVC BLOCKING 2. PROVIDE OSA ON NEW UNITS 3. PROVIDE AIR BALANCE REPORT 4. UNIT OVERFUSED (6) 5. COAT ALL DUCT ON ROOF PER CONVERSATION |
|
| 08/26/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |