Permit: T07CM03988

Parcel: 11706183A


Addresses:

1 N 5TH AV


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T07CM03988

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
09/23/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
09/22/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
09/17/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
07/07/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
FILTER ASSEMBLY OK
05/07/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. CONDENSATE VENTS SHALL TERMINATE AT A HEIGHT ABOVE THE OUTLET OF DRAIN PAN
2. FINISH INSULATING CONDENSATE AND CWP LINES
3. MAKE SURE BALANCE CONTROL VALVES ARE ACCESSIBLE FOR BALANCING G.P.M
04/28/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
04/21/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
6TH, 5TH, 4TH, 3RD FLOORS DUCT SEAL OK
FINISH CONDENSATE
OK FOR ROCK
04/16/2008 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE FILTER RACKS OR APPROVED METHOD OF SUPPORTING FILTERS IN UNITS
2. SEAL JOINTS ON S-DRIVE OF NEW DUCT
3. INSULATE NEW DUCT WITH DUCT WRAP

NOTE: CALL INSPECTION ON DUCT SEAL PRIOR TO INSULATING DUCT