Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T07CM03988
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/23/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
09/22/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
09/17/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
07/07/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* FILTER ASSEMBLY OK |
|
05/07/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. CONDENSATE VENTS SHALL TERMINATE AT A HEIGHT ABOVE THE OUTLET OF DRAIN PAN 2. FINISH INSULATING CONDENSATE AND CWP LINES 3. MAKE SURE BALANCE CONTROL VALVES ARE ACCESSIBLE FOR BALANCING G.P.M |
|
04/28/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
04/21/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 6TH, 5TH, 4TH, 3RD FLOORS DUCT SEAL OK FINISH CONDENSATE OK FOR ROCK |
|
04/16/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE FILTER RACKS OR APPROVED METHOD OF SUPPORTING FILTERS IN UNITS 2. SEAL JOINTS ON S-DRIVE OF NEW DUCT 3. INSULATE NEW DUCT WITH DUCT WRAP NOTE: CALL INSPECTION ON DUCT SEAL PRIOR TO INSULATING DUCT |