Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03988
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/27/2010 | ELECTRIC - FINAL | Approved | ||
09/26/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK BUILDING AS DISCUSSED WITH LEERAY RECEIVED GENERATOR TEST |
|
09/23/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK UNITS 1ST FLOOR OK PENTHOUSE AND ELEVATORS 1. FILL UNUSED OPENING IN FRONT PANEL EDS 2. LABEL SERVICE DISCONNECTS 3. GENERATOR LABELING NEEDED PER 702.8 OR 703.8 4. NEED COPY OF GENERATOR TEST |
|
09/22/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. MISSING RANGES 2. WALL NOT DRYWALLED AND MISSING LIGHT AND GFCI 3. MULTIPLE CONDUCTORS UNDER LUG 4. USE APPROVED CONNECTORS WITH M/C A/C CHANGES FOR THERMOSTAT: FILL UNUSED OPENINGS NOT EMPTY M/C CONNECTOR |
|
09/17/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
09/08/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TCO FOR FLOORS 2 & 3 SUBJECT TO OTHER INSPECTORS APPROVAL |
|
09/05/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CONTR. PERSONNEL NOT ON SITE - RECALL INSP. GATES LOCKEDE |
|
09/03/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK 2ND & 3RD FLOORS AFTER CORRECTIONS PENTHOUSE: 1. SUPPORT CONDUIT 2. TIGHTEN LOOSE FITTINGS 3. BOX OVERFILLED 4. FILL UNUSED OPENING 5. USE APPROVED FITTINGS FOR M/C CABLE 2ND & 3RD FLOORS: 1. #302 EXCESS PAINT ON BREAKER FACES - UNLEGIBLE 2. RECEPTACLES IN INDUSTRIAL COVER MISSING SCREWS 3. USE APPROVED FITTINGS WITH M/C CABLE |
|
09/02/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. MAINTAIN WORKING CLEARANCES NEW PANEL "3A" -- 110.26 2. BOX OVERFILLED 3. CANNOT USE SHEETMETAL THREAD SCREWS FOR GROUNDING 4. KITCHEN COUNTER GFCI NOT WORKING 5. VERIFY WATER SENSOR VOLTAGE - IF 120V NEED JUNCTION BOXES 6. FINISH MAKE UP AIR HANDLER |
|
08/20/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* UNITS: 1. FINISH BOX EXTENDERS 2. CIRCUIT DIRECTORIES HALLS: 1. FINISH EXIT LIGHTS |
|
08/19/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* UNITS 1. BOXES IN NON-COMBUSTIBLES MORE THAN 1/4" BOX TO SURFACE 314.20 2. PROPERLY GROUND SUB-PANELS 3. RECEPTACLES IN INDUSTRIAL COVERS - SCREWS #601 MISSING BATH GFI #605 MISSING RECEPTACLE |
|
08/13/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 6TH FLOOR: A. LAUNDRY ROOM: 1. PROTECT CATV CABLES FROM SHARP METAL EDGES ENTERING BOXES 2. GROUND RECEPTACLES B. UNITS 1. ANTI-TIPS FOR RANGES 2. REVISE CIRCUIT DIRECTORIES PER 408.4 3. EXISTING RECEPTACLE NOT GROUNDED TO BOX 4. SEPARATE GROUNDS AND NEUTRALS SUB-PANELS C. HALLS 1. FINISH BOX MAKE-UP 2. FILL UNUSED OPENINGS BOXES 3. CLEAN DIRT FROM PANELS 4. EXIT LIGHTS 700.12 |
|
08/04/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SYSTEM VERIFIED AS GROUNDED - RECEPTACLE NEEDS TO BE GROUNDED TO BOXES 2. FINISH MAKE UP IN WALL 3. GROUND NEEDED FOR ALL RECEPTACLES 4. SEPARATE GROUNDS AND NEUTRALS AT SUB-PANELS 5. EXIT LIGHTS TO BE ON CORRIDOR CIRCUIT AS PLANS AND 700.12 |
|
07/29/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOXES OVERFILLED 2. VDV SUPPORT FALLING DOWN 3. FIRE ALARM BOXES TO BE RED ALSO - NOT JUST COVERS 4. NEED CIRCUIT DIRECTORIES AS PER 408.4 ALL PANELS 5. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM PANELS 6. CLEAN SURFACE UNDER LUGS & SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING 250.12 & 250.8 7. BOXES MORE THAN 1/4" OR FLUSH IN COMBUSTIBLES NEED APPROVED EXTENDER RINGS 314.20 8. MISSING COVERS 9. GROUNDED RECEPTACLES ON AN UNGROUNDED SYSTEM 10. MAKE UP RANGE *PARTIAL INSPECTION ONLY |