Permit: T07CM03988

Parcel: 11706183A


Addresses:

1 N 5TH AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM03988

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/27/2010 ELECTRIC - FINAL Approved
09/26/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK BUILDING AS DISCUSSED WITH LEERAY
RECEIVED GENERATOR TEST
09/23/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK UNITS 1ST FLOOR
OK PENTHOUSE AND ELEVATORS

1. FILL UNUSED OPENING IN FRONT PANEL EDS
2. LABEL SERVICE DISCONNECTS
3. GENERATOR LABELING NEEDED PER 702.8 OR 703.8
4. NEED COPY OF GENERATOR TEST
09/22/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. MISSING RANGES
2. WALL NOT DRYWALLED AND MISSING LIGHT AND GFCI
3. MULTIPLE CONDUCTORS UNDER LUG
4. USE APPROVED CONNECTORS WITH M/C

A/C CHANGES FOR THERMOSTAT: FILL UNUSED OPENINGS NOT EMPTY M/C CONNECTOR
09/17/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
09/08/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK TCO FOR FLOORS 2 & 3
SUBJECT TO OTHER INSPECTORS APPROVAL
09/05/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CONTR. PERSONNEL NOT ON SITE - RECALL INSP.
GATES LOCKEDE
09/03/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK 2ND & 3RD FLOORS AFTER CORRECTIONS

PENTHOUSE:
1. SUPPORT CONDUIT
2. TIGHTEN LOOSE FITTINGS
3. BOX OVERFILLED
4. FILL UNUSED OPENING
5. USE APPROVED FITTINGS FOR M/C CABLE

2ND & 3RD FLOORS:
1. #302 EXCESS PAINT ON BREAKER FACES - UNLEGIBLE
2. RECEPTACLES IN INDUSTRIAL COVER MISSING SCREWS
3. USE APPROVED FITTINGS WITH M/C CABLE
09/02/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. MAINTAIN WORKING CLEARANCES NEW PANEL "3A" -- 110.26
2. BOX OVERFILLED
3. CANNOT USE SHEETMETAL THREAD SCREWS FOR GROUNDING
4. KITCHEN COUNTER GFCI NOT WORKING
5. VERIFY WATER SENSOR VOLTAGE - IF 120V NEED JUNCTION BOXES
6. FINISH MAKE UP AIR HANDLER
08/20/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
UNITS:
1. FINISH BOX EXTENDERS
2. CIRCUIT DIRECTORIES

HALLS:
1. FINISH EXIT LIGHTS
08/19/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
UNITS
1. BOXES IN NON-COMBUSTIBLES MORE THAN 1/4" BOX TO SURFACE 314.20
2. PROPERLY GROUND SUB-PANELS
3. RECEPTACLES IN INDUSTRIAL COVERS - SCREWS

#601 MISSING BATH GFI
#605 MISSING RECEPTACLE
08/13/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
6TH FLOOR:
A. LAUNDRY ROOM:
1. PROTECT CATV CABLES FROM SHARP METAL EDGES ENTERING BOXES
2. GROUND RECEPTACLES

B. UNITS
1. ANTI-TIPS FOR RANGES
2. REVISE CIRCUIT DIRECTORIES PER 408.4
3. EXISTING RECEPTACLE NOT GROUNDED TO BOX
4. SEPARATE GROUNDS AND NEUTRALS SUB-PANELS

C. HALLS
1. FINISH BOX MAKE-UP
2. FILL UNUSED OPENINGS BOXES
3. CLEAN DIRT FROM PANELS
4. EXIT LIGHTS 700.12
08/04/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SYSTEM VERIFIED AS GROUNDED - RECEPTACLE NEEDS TO BE GROUNDED TO BOXES
2. FINISH MAKE UP IN WALL
3. GROUND NEEDED FOR ALL RECEPTACLES
4. SEPARATE GROUNDS AND NEUTRALS AT SUB-PANELS
5. EXIT LIGHTS TO BE ON CORRIDOR CIRCUIT AS PLANS
AND 700.12
07/29/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOXES OVERFILLED
2. VDV SUPPORT FALLING DOWN
3. FIRE ALARM BOXES TO BE RED ALSO - NOT JUST COVERS
4. NEED CIRCUIT DIRECTORIES AS PER 408.4 ALL PANELS
5. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM PANELS
6. CLEAN SURFACE UNDER LUGS & SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING 250.12 & 250.8
7. BOXES MORE THAN 1/4" OR FLUSH IN COMBUSTIBLES NEED APPROVED EXTENDER RINGS 314.20
8. MISSING COVERS
9. GROUNDED RECEPTACLES ON AN UNGROUNDED SYSTEM
10. MAKE UP RANGE

*PARTIAL INSPECTION ONLY