Permit: T07CM03988

Parcel: 11706183A


Addresses:

1 N 5TH AV


Inspection Status: Approved

Inspection History: FIREWALL/FIREBARRIER/FIRESTOP

Permit Number - T07CM03988

Inspection Description - FIREWALL/FIREBARRIER/FIRESTOP

Inspection Status - Approved

Date Description Inspector Results Comments
09/23/2008 FIREWALL/FIREBARRIER/FIRESTOP Approved IVRS - Inspection :*
09/22/2008 FIREWALL/FIREBARRIER/FIRESTOP Not ready for Inspection IVRS - Inspection :*
09/17/2008 FIREWALL/FIREBARRIER/FIRESTOP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 1ST FLOOR CORRIDOR INCOMPLETE
2. MISSING FIRE DAMPERS @ KITCHENS
3. OPEN CONDUIT BOTH SIDES OF HALL
4. I NEED TO CHECK ON FIRE DAMPER EXCEPTION
08/11/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
1ST FLOOR DWELLING UNITS - GROUT AROUND PIPE UNIT 111
REPAIR CHASE UNIT 103
07/23/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
2ND FLOOR ROOMS DONE

A COUPLE OF CONDUITS & HOLES IN HALL REMAIN
07/18/2008 FIREWALL/FIREBARRIER/FIRESTOP Denied IVRS - Inspection :
See detailed listing on site.| 999*
ELECTRIC ROOM & CHASE AT END OF HALL COVERED WITHOUT INSPECTION - ROOM 214 INCORRECT IN BATH
ROOM 208 INCORRECT BEHIND SINK

PLEASE REMOVE TRASH & DEBRIS COVERING WALKWAY TO EAST ROOMS - INSPECTION STOPPED!
07/08/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
3RD FLOOR OK; 4TH FLOOR OK
PROVIDE ACCESS TO 500, 501, 502
06/25/2008 FIREWALL/FIREBARRIER/FIRESTOP Denied IVRS - Inspection :
See detailed listing on site.| 999*
3RD FLOOR PLEASE HAVE YOUR DRYWALL CONTRACTOR CONSULT THE US GYPSUM MANUAL FOR PROPER ROCK INSTALLATION.

MAX 1/8" GAP IS ALLOWED AT BUTT JOINTS
SEE NOTES FROM 6/10
ALSO, ROOMS 500, 501, 502, 503

HAVE NOT BEEN CORRECTED YET
4TH FLOOR ELEC. ROOM STILL NOT DONE
06/20/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
4TH FLOOR DWELLING UNITS OK
ELECTRIC ROOM NOT DONE
06/19/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
LEVEL 6 COMPLETE - HOORAY

LEVEL 5 -
A. ROOM 3RD EAST FROM ELEVATOR ON SOUTH SIDE
BLOCK REMOVED AT KITCHEN WATER SUPPLY
B. 2ND ROOM FROM ELEVATOR NO FIRESTOP @ LAVATORY
06/10/2008 FIREWALL/FIREBARRIER/FIRESTOP Not ready for Inspection IVRS - Inspection :*
NO MORE THAN 1/8" GAP ALLOWED SHEETROCK JOINTS
YOU MAY PATCH UP TO 144 IN WITHOUT GOING STUD TO STUD
FIX ALL ROCK, FIRESTOP ALL FIRE BARRIER PENETRATIONS
THEN RECALL
06/09/2008 FIREWALL/FIREBARRIER/FIRESTOP Not ready for Inspection IVRS - Inspection :*
CANCELED
06/02/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
1. 6TH FLOOR CMU WALLS ONLY (EXCEPT UTILITY ROOM)
2. 5TH FLOOR CMU WALLS (EXCEPT UTILITY ROOM)
3. OK TO SET KITCHEN CABINETS - 3RD FLOOR
4. ALL CMU WALLS OK LEVEL 2
OK TO ROCK LEVEL 2
NEED TO SEE FLOORS 211, 213, 215
WHEN PENETRATIONS DONE
05/21/2008 FIREWALL/FIREBARRIER/FIRESTOP Not ready for Inspection IVRS - Inspection :*
1. HAVE AN ENTIRE FLOOR DONE!
2. FIRE STOP ALL APPLICABLE LOCATIONS
3. DO NOT HAVE EQUIPMENT IN WAY
05/13/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval IVRS - Inspection :*
OK TO ROCK 3-6
04/28/2008 FIREWALL/FIREBARRIER/FIRESTOP Partial Approval 2-21-08
1. PROVIDE COMPLETE FIRESTOP SYSTEM TO REPLACE ALL OLD PENETRATION SEALANT AND NEW PENETRATIONS IN CORRIDOR WALLS AND FLOORS. REF: PP A4.0 FLOOR SYSTEM PROVIDED WALL SYSTEM INCOMPLETE
2. DO NOT COVER ANY AREAS WITH PENETRATIONS UNTIL AFTER INSPECTION

3-20-08
YOU MUST FIRESTOP PER PLAN PER CODE
NO EXEMPTIONS FOR EXISTING BUILDING

4-21-08
WHILE 6TH FLOOR INTUMESCENT APPLICATIONS ARE OK YOU HAVE NOT COMPLETED ALL PENETRATION FIRESTOP. ALSO, YOU ARE NOT GOING TO BE ABLE TO SWAP TO PVC AT DWV SYSTEM
ALSO, MOST OF YOUR CLOSET FLANGES MAY NOT BE REUSED

4-28-08
1) INSPECTION CALLED IN FOR 4TH & 5TH FLOOR BUT INSPECTION WAS STOPPED AT 4TH FLOOR.

A) I NEED TO SEE CLOSET FLANGES CLEANED UP AS I DO NOT BELIEVE YOU WILL BE ABLE TO KEEP THEM. I CANNOT PASS A FIRES STOP INSPECTION WHEN I KNOW IT WILL BE ALTERED.

B) WHY AREN'T YOU INSTALING ALL FIRESTOP? DATA CONDUITS AND SOME PLUMBING PENETRATIONS ARE INCOMPLETE.

C) WHY ISN'T FRAMING IN FOR SHEETROCK REPLACEMENT @ ACCESS HOLES.