Inspection History Details
Inspection Status: Approved
Inspection History: FIREWALL/FIREBARRIER/FIRESTOP
Permit Number - T07CM03988
Inspection Description - FIREWALL/FIREBARRIER/FIRESTOP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/23/2008 | FIREWALL/FIREBARRIER/FIRESTOP | Approved | IVRS - Inspection :* | |
09/22/2008 | FIREWALL/FIREBARRIER/FIRESTOP | Not ready for Inspection | IVRS - Inspection :* | |
09/17/2008 | FIREWALL/FIREBARRIER/FIRESTOP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 1ST FLOOR CORRIDOR INCOMPLETE 2. MISSING FIRE DAMPERS @ KITCHENS 3. OPEN CONDUIT BOTH SIDES OF HALL 4. I NEED TO CHECK ON FIRE DAMPER EXCEPTION |
|
08/11/2008 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | IVRS - Inspection :* 1ST FLOOR DWELLING UNITS - GROUT AROUND PIPE UNIT 111 REPAIR CHASE UNIT 103 |
|
07/23/2008 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | IVRS - Inspection :* 2ND FLOOR ROOMS DONE A COUPLE OF CONDUITS & HOLES IN HALL REMAIN |
|
07/18/2008 | FIREWALL/FIREBARRIER/FIRESTOP | Denied | IVRS - Inspection : See detailed listing on site.| 999* ELECTRIC ROOM & CHASE AT END OF HALL COVERED WITHOUT INSPECTION - ROOM 214 INCORRECT IN BATH ROOM 208 INCORRECT BEHIND SINK PLEASE REMOVE TRASH & DEBRIS COVERING WALKWAY TO EAST ROOMS - INSPECTION STOPPED! |
|
07/08/2008 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | IVRS - Inspection :* 3RD FLOOR OK; 4TH FLOOR OK PROVIDE ACCESS TO 500, 501, 502 |
|
06/25/2008 | FIREWALL/FIREBARRIER/FIRESTOP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 3RD FLOOR PLEASE HAVE YOUR DRYWALL CONTRACTOR CONSULT THE US GYPSUM MANUAL FOR PROPER ROCK INSTALLATION. MAX 1/8" GAP IS ALLOWED AT BUTT JOINTS SEE NOTES FROM 6/10 ALSO, ROOMS 500, 501, 502, 503 HAVE NOT BEEN CORRECTED YET 4TH FLOOR ELEC. ROOM STILL NOT DONE |
|
06/20/2008 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | IVRS - Inspection :* 4TH FLOOR DWELLING UNITS OK ELECTRIC ROOM NOT DONE |
|
06/19/2008 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | IVRS - Inspection :* LEVEL 6 COMPLETE - HOORAY LEVEL 5 - A. ROOM 3RD EAST FROM ELEVATOR ON SOUTH SIDE BLOCK REMOVED AT KITCHEN WATER SUPPLY B. 2ND ROOM FROM ELEVATOR NO FIRESTOP @ LAVATORY |
|
06/10/2008 | FIREWALL/FIREBARRIER/FIRESTOP | Not ready for Inspection | IVRS - Inspection :* NO MORE THAN 1/8" GAP ALLOWED SHEETROCK JOINTS YOU MAY PATCH UP TO 144 IN WITHOUT GOING STUD TO STUD FIX ALL ROCK, FIRESTOP ALL FIRE BARRIER PENETRATIONS THEN RECALL |
|
06/09/2008 | FIREWALL/FIREBARRIER/FIRESTOP | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
06/02/2008 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | IVRS - Inspection :* 1. 6TH FLOOR CMU WALLS ONLY (EXCEPT UTILITY ROOM) 2. 5TH FLOOR CMU WALLS (EXCEPT UTILITY ROOM) 3. OK TO SET KITCHEN CABINETS - 3RD FLOOR 4. ALL CMU WALLS OK LEVEL 2 OK TO ROCK LEVEL 2 NEED TO SEE FLOORS 211, 213, 215 WHEN PENETRATIONS DONE |
|
05/21/2008 | FIREWALL/FIREBARRIER/FIRESTOP | Not ready for Inspection | IVRS - Inspection :* 1. HAVE AN ENTIRE FLOOR DONE! 2. FIRE STOP ALL APPLICABLE LOCATIONS 3. DO NOT HAVE EQUIPMENT IN WAY |
|
05/13/2008 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | IVRS - Inspection :* OK TO ROCK 3-6 |
|
04/28/2008 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | 2-21-08 1. PROVIDE COMPLETE FIRESTOP SYSTEM TO REPLACE ALL OLD PENETRATION SEALANT AND NEW PENETRATIONS IN CORRIDOR WALLS AND FLOORS. REF: PP A4.0 FLOOR SYSTEM PROVIDED WALL SYSTEM INCOMPLETE 2. DO NOT COVER ANY AREAS WITH PENETRATIONS UNTIL AFTER INSPECTION 3-20-08 YOU MUST FIRESTOP PER PLAN PER CODE NO EXEMPTIONS FOR EXISTING BUILDING 4-21-08 WHILE 6TH FLOOR INTUMESCENT APPLICATIONS ARE OK YOU HAVE NOT COMPLETED ALL PENETRATION FIRESTOP. ALSO, YOU ARE NOT GOING TO BE ABLE TO SWAP TO PVC AT DWV SYSTEM ALSO, MOST OF YOUR CLOSET FLANGES MAY NOT BE REUSED 4-28-08 1) INSPECTION CALLED IN FOR 4TH & 5TH FLOOR BUT INSPECTION WAS STOPPED AT 4TH FLOOR. A) I NEED TO SEE CLOSET FLANGES CLEANED UP AS I DO NOT BELIEVE YOU WILL BE ABLE TO KEEP THEM. I CANNOT PASS A FIRES STOP INSPECTION WHEN I KNOW IT WILL BE ALTERED. B) WHY AREN'T YOU INSTALING ALL FIRESTOP? DATA CONDUITS AND SOME PLUMBING PENETRATIONS ARE INCOMPLETE. C) WHY ISN'T FRAMING IN FOR SHEETROCK REPLACEMENT @ ACCESS HOLES. |