Permit: T07CM03987

Parcel: 105097340

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T07CM03987

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
03/18/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
03/03/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
02/28/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HAVE OVERFILLED J-BOX - NEC 311.16
2. HAVE OVERFILLED/WRONG COMBINATION OF WIRE NUTS
NEC 110.3B (SEE WIRENUT BAG OR BOX INSTRUCTIONS)
3. STILL HAVE FIXTURES TO INSTALL
4. LOW VOLTAGE WIRING TO BE PROPERLY SUPPORTED TO STRUCTURE NOT LAYING ON OTHER EQUIPMENT
5. EMERGENCY LIGHT TEST SWITCHES TO BE CUT INTO GRID
NOT LEFT ABOVE GRID
6. EMT TO BE SECURED WITHIN 36" OF ENCLOSURES -
NEC 358.30
7. REMOVE TEMP WIRING FROM CEILING
8. AT AIR HANDLERS - STRAP FLEX WITHIN 12" OF ENCLOSURES, INSTALL FUSES, NEED GREEN EQUIPMENT GROUND
9. SUPPORT MC @ MAX 6' INTERVALS - NEC 330.30
02/11/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO COVER HARD LIDS