Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM03987
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/18/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 03/03/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 02/28/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HAVE OVERFILLED J-BOX - NEC 311.16 2. HAVE OVERFILLED/WRONG COMBINATION OF WIRE NUTS NEC 110.3B (SEE WIRENUT BAG OR BOX INSTRUCTIONS) 3. STILL HAVE FIXTURES TO INSTALL 4. LOW VOLTAGE WIRING TO BE PROPERLY SUPPORTED TO STRUCTURE NOT LAYING ON OTHER EQUIPMENT 5. EMERGENCY LIGHT TEST SWITCHES TO BE CUT INTO GRID NOT LEFT ABOVE GRID 6. EMT TO BE SECURED WITHIN 36" OF ENCLOSURES - NEC 358.30 7. REMOVE TEMP WIRING FROM CEILING 8. AT AIR HANDLERS - STRAP FLEX WITHIN 12" OF ENCLOSURES, INSTALL FUSES, NEED GREEN EQUIPMENT GROUND 9. SUPPORT MC @ MAX 6' INTERVALS - NEC 330.30 |
|
| 02/11/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO COVER HARD LIDS |