Inspection History Details
Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
Permit Number - T07CM03980
Inspection Description - REINFORCED MASONRY PRE-GROUT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/06/2008 | REINFORCED MASONRY PRE-GROUT | Approved | IVRS - Inspection :* | |
02/04/2008 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLY WITH DETAIL S1/A2 S2/A2 2) 2-#4 BOND BEAM AT BOLT HEIGHT |
|
01/31/2008 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO NOTCH FOR BOND BEAM TO HAVE MINIMUM COVERAGE OVER REBAR |
|
01/16/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) 2ND LIFT OK |
|
01/14/2008 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING LINTEL OVER DOOR WAY-OPENING |
|
12/27/2007 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) INSPECTED FIRST LIFT-OK TO CONTINUE |