Permit: T07CM03974

Parcel: 13601008J

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T07CM03974

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
01/25/2008 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
WATER TEST FROM INTERIOR OF BLD TO 2' PAST EXTERIOR CLEANOUT ONLY

CALL IN 03015 PRIOR TO CONCRETE
01/23/2008 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSTALL PER APPROVED PLAN, PLAN CALLS FOR 3" MOP SINK
WHERE IS THE 3" PIPING AND P-TRAP
FAILURE TO COMPLY WILL RESULT IN REFEE
01/17/2008 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PIPING TO BE INSTALLED PER APPROVED PLAN WITH MINIMUM 1/4" PER FOOT FALL
2. IF A BACKWATER VALVE IS INSTALLED A VENT WILL BE REQUIRED PER 904.1 2006 UPC REQUIREMENTS DOWNSTREAM OF BACK WATER VALVE TO EQUAL CROSS SECTIONAL AREA OF REQUIRED BCD DRAIN
3. PROVIDE A CITY APPROVED SITE PLAN OF CONTINUATION
OF BUILDING SEWER AND HAVE YOUR YELLOW PERMIT CARD ON SITE.