Permit: T07CM03966

Parcel: 140292060


Addresses:

3601 E BRITANNIA DR

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
11/04/2008 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
09/22/2008 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
HYDRONIC PRESSURE TEST COMPLETE ALL OK
09/18/2008 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
TEST PRESS. IS TO BE 100 PSI OR 1.5 TIMES MAXIMUM OPERATING PRESSURE WHICHEVER IS GREATER
08/04/2008 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
CHILLER PIPING FROM EXTERIOR PENETRATION TO ROOF PENETRATIONS OK TO INSULATE
PRESSURE TEST OK
07/29/2008 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
SECOND FLOOR RESTROOMS OK FOR ROCK MECHANICAL ONLY
07/22/2008 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1ST FLOOR RESTROOM OK TO ROCK
07/08/2008 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1ST FLOOR EAST RESTROOMS OK TO INSULATE
1ST FLOOR WEST RESTROOMS OK TO INSULATE