Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/14/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* RECEIVED FIELD REPORT FOR EM. GEN. |
|
| 11/12/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE PAPERWORK FOR GEN/TRANSFER SWITCH TEST OK FOR TCO |
|
| 11/03/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. INSTALL CAUTION LABEL ON SES EQUIP. TO WARN ABOUT GENERATOR BACKUP SOURCE 700 NEC 2. CHECK ALL LIGHT POLES FOR PROPER GROUNDING 3. LTG. AT LOBBY (SOUTH) MISSING TRIM 4. OFFICE PARTITIONS TO COMPLY WITH 605.6 & 7 NEC |