Permit: T07CM03966

Parcel: 140292060


Addresses:

3601 E BRITANNIA DR

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
11/12/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/22/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO ENERGIZE "M" PANELS, OK TO TEMP LTG.
09/18/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. 480V POWER PANEL NEED WORKING CLEARANCE
AS PER 110.26 - 3 1/2 STEEL COLUMN IN WORKING SPACE
2. PANELS IN ELECTRIC ROOM NEED TO MATCH
PLAN 2ND FLOOR WEST ELECTRIC ROOM
09/11/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ELECTRIC ROOM, EXCEPT 2ND FLOOR WEST NOT READY
08/07/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) 2ND FLOOR RESTROOMS, SERVER ROOM, TELEPHONE ROOM WALLS OK
07/29/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 2ND FLOOR WALLS, EXCEPT SERVER ROOM WALLS
OK HARD LIDS 1ST FLOOR
07/22/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK WALLS 1ST FLOOR
2. CLEARANCES FOR SERVICE AND TRANSFER EQUIP. TO COMPLY WITH 110.26 A-1A FOR BACK & SIDES