Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/12/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/22/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO ENERGIZE "M" PANELS, OK TO TEMP LTG. |
|
| 09/18/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. 480V POWER PANEL NEED WORKING CLEARANCE AS PER 110.26 - 3 1/2 STEEL COLUMN IN WORKING SPACE 2. PANELS IN ELECTRIC ROOM NEED TO MATCH PLAN 2ND FLOOR WEST ELECTRIC ROOM |
|