Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03953
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/11/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/08/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND FOR PHONE BOARD TO BE PER NEC 800.100 SEE PLAN 2. PROVIDE GFI PROTECTION FOR FOOD PREP REFER - NEC 210.8 B2 3. ON ROOF: SECURE SIGN EMT; EQUIPMENT TO BE IDENTIFIED AS IT IS IN PANEL DIRECTORY 4. HOOD CONTROL PANEL TO BE ACCESSIBLE MECHANICAL FINAL TODAY |
|
04/02/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INTERIOR INSPECTION 1. NEED GROUND TO PHONE BOARD - SEE PLAN WALK IN FRIDGE 1. OVERCURRENT PROTECTION TO BE PER DATA PLATE 2. PROPERLY GROUND J-BOXES SHEETMETAL SCREWS NOT ALLOWED 3. SEAL RACEWAYS ENTERING UNIT 4. STRAP MC WITHIN 12" OF TERMINATIONS WATER HEATER 1. STRAP MC WITHIN 12" OF TERMINATIONS 2. MISSING SCREW IN CONNECTOR EMERGENCY LIGHTING 1. ENERGIZE AS SHOWN ON PLAN FOOD PREP REFER 1. PROVIDE RECEPTACLE FOR - CORD NOT TO RUN THROUGH WALL MECHANICAL SYSTEM TO BE WIRED PER PLAN/TO FOLLOW SEQUENCE OF OPERATION STILL NEED TO LOOK AT INTERLOCK/HOOD WIRING |
|
03/27/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ON ROOF 1. FOR SIGN CKT - SUPPORT J-BOX, GROUND SCREW LOOSE, SEAL FLASHING, FLEX NOT ALLOWED WHERE SUBJECT TO PHYSICAL DAMAGE, NOT PROPERLY SECURED/SUPPORTED, TIGHTEN FITTINGS 2. IDENTIFY MVA DISCONNECTS, SECURE TO STRUCTURE, TIGHTEN FITTINGS 3. IDENTIFY EX HOODS ON ROOF INSPECTION FOR INTERIOR NEXT TRIP - WORK IN PROGRESS |