Permit: T07CM03953

Parcel: 12404102B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM03953

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/11/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/08/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUND FOR PHONE BOARD TO BE PER NEC 800.100
SEE PLAN
2. PROVIDE GFI PROTECTION FOR FOOD PREP REFER -
NEC 210.8 B2
3. ON ROOF: SECURE SIGN EMT; EQUIPMENT TO BE IDENTIFIED AS IT IS IN PANEL DIRECTORY
4. HOOD CONTROL PANEL TO BE ACCESSIBLE

MECHANICAL FINAL TODAY
04/02/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INTERIOR INSPECTION

1. NEED GROUND TO PHONE BOARD - SEE PLAN

WALK IN FRIDGE
1. OVERCURRENT PROTECTION TO BE PER DATA PLATE
2. PROPERLY GROUND J-BOXES SHEETMETAL SCREWS NOT ALLOWED
3. SEAL RACEWAYS ENTERING UNIT
4. STRAP MC WITHIN 12" OF TERMINATIONS

WATER HEATER
1. STRAP MC WITHIN 12" OF TERMINATIONS
2. MISSING SCREW IN CONNECTOR

EMERGENCY LIGHTING
1. ENERGIZE AS SHOWN ON PLAN

FOOD PREP REFER
1. PROVIDE RECEPTACLE FOR - CORD NOT TO RUN THROUGH WALL

MECHANICAL SYSTEM TO BE WIRED PER PLAN/TO FOLLOW SEQUENCE OF OPERATION

STILL NEED TO LOOK AT INTERLOCK/HOOD WIRING
03/27/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ON ROOF
1. FOR SIGN CKT - SUPPORT J-BOX, GROUND SCREW LOOSE, SEAL FLASHING, FLEX NOT ALLOWED WHERE SUBJECT TO PHYSICAL DAMAGE, NOT PROPERLY SECURED/SUPPORTED, TIGHTEN FITTINGS
2. IDENTIFY MVA DISCONNECTS, SECURE TO STRUCTURE, TIGHTEN FITTINGS
3. IDENTIFY EX HOODS ON ROOF

INSPECTION FOR INTERIOR NEXT TRIP - WORK IN PROGRESS