Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/04/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 10/30/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* NEED TEST ON CARBON MONOXIDE SENSORS EVERYTHING ELSE OK |
|
| 09/30/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. PROVIDE A SLEEVE AROUND REFER LINES AT WALL PENETRATION TO OUTDOORS 2. PROVIDE AIR BALANCE REPORT 3. PROVIDE TEST ON CARBON MONOXIDE SENSORS 4. PROVIDE FILTERS IN FRESH AIR INTAKE 5. PROVIDE DRAINS ON EVAP. COOLERS 6. PLANS REQUIRE OVERFLOW PAN FOR COOLERS DRAIN TO DAYLIGHT 7. MARK FAN COIL DATA PLATES W/PROPER HEAT STRIP INSTALLED AND FUSE ACCORDINGLY 8. PERMANENTLY I.D ALL EQUIPMENT |