Permit: T07CM03944

Parcel: 14103024C


Addresses:

6450 E VALENCIA RD

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/17/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
RECEIVED BACTERIA REPORT FOR POTABLE WATER
RECEIVED LANDSCAPING BACKFLOW CERTIFICATION
11/13/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
COMPLETE LIST FROM 10/30/08
10/30/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. VENT FROM DUMP STATION TO TERMINATE
VERTICAL 1' FROM BUILDING SIDE WALL
2. CALL IN PERMIT #T07PL01694 FOR FINAL
3. HAVE BACTERIA REPORT & BACKFLOW CERTIFICATION
ON SITE
09/30/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
LIST MAY NOT BE COMPLETE

CALL IN ALL PLUMBING INSPECTIONS ON YELLOW PERMIT CARD THAT HAVE NOT BEEN APPROVED

TERMINATE ALL CLEANOUTS, INTERIOR AND EXTERIOR PROPERLY, EXTERIOR WHERE IS TRACER WIRE AT SURFACE.

1. EXTERIOR VENT FROM DUMP STATION SHALL TERMINATE 6" ABOVE ROOF LINE OR 1' FROM BUILDING SIDE WALL, WITH VERTICAL TERMINATION MINIMUM 10' FROM FINISH GRADE
2. WATER HEATER REQUIRES DRIP PAN WITH DRAIN
TO APPROVED LOCATION WHEN ON ELEVATED PLATFORM
PER PLAN.
3. PUBLIC USE LAVS REQUIRE TEMPERING TO MEET 110 DEG. MAX. TEMPERATURE ON HOT SIDE
4. PROVIDE CLEAN BACTERIA REPORT FOR POTABLE WATER SUPPLY. NOTE #8 P1-1
5. PROVIDE APPROVED BACKFLOW PROTECTION FOR LANDSCAPING WATER SUPPLY WITH CERTIFICATION
6. PROVIDE WATER HAMMER ARRESTORS FOR WASHING MACHINE BOX - HOT & COLD SUPPLY