Permit: T07CM03944

Parcel: 14103024C


Addresses:

6450 E VALENCIA RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/13/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/30/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. STILL MISSING EXITS AND EM LIGHTS -- INSTALL PER PLAN
2. CARBON MONOXIDE DETECTORS NOT WORKING
09/30/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED REVISION TO PLANS FOR REMOVAL OF WALL
IT APPEARS ENTIRE AREA IS NOW A SHOP AREA AND NEEDS TO BE CLASSIFIED IF HAZARDOUS AREA
2. REVISE PLANS FOR CHANGES TO AIR HANDLERS AND HEAT PUMPS - MARK NAMEPLATE DATA
3. CARBON MONOXIDE EXHAUST FAN IN HAZARDOUS LOCATION PLAN CALLS FOR FAN TO BE MOUNTED @ 17', SEE M1-1
4. MISSING EM LIGHT AND EXIT