Permit: T07CM03944

Parcel: 14103024C


Addresses:

6450 E VALENCIA RD

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
11/13/2008 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
09/03/2008 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
1) BONDING JUMPERS TO 2" RACEWAYS AT DISCONNECTS TO GUTTER NOT SIZED PROPERLY 100 AMP NEEDS #6 & 200 AMPS NEEDS #4 NEC 250.102 & 250.66
2) ADD SERVICE DISCONNECT LABELS TO DISCONNECTS
08/27/2008 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED TO POST BOND FOR RELEASE OF POWER
2. INSTALL FUSES
3. MARK "SERVICE DISCONNECTS" - "1 OF 2" AND "2 OF 2"
4. TIGHTEN SCREWS ON BONDING LOCKNUTS
5. BOND CHASE NIPPLE
6. ARRANGE GROUNDING CONDUCTORS TO REMOVE OBJECTIONABLE CURRENT
7. HAVE GUTTERS OPEN FOR INSPECTION
8. SERICE CONDUTORS NOT SIZED PER PLAN
9. ENSURE ALL SERVICE RACEWAYS PROPERLY BONDED
10. DOES GUTTER REQUIRE HUBS?
06/02/2008 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
1. OK 2 - 4" PVC FROM SES TO TEP XFMR
2. INSTALL WARNING RIBBON ABOVE RACEWAYS
PER NEC 300.5
05/30/2008 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLAN CALLS FOR 2 - 4" RACEWAYS TO BUILDING
2. PLAN CALLS FOR 600 MCM TEP ALLOWS MAX. OF 500 MCM
3. PLAN DOES NOT COVER 4" RACEWAY TO BUILDING #2