Permit: T07CM03944

Parcel: 14103024C


Addresses:

6450 E VALENCIA RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
11/13/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/02/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. HAVE APPROVED ELECTRIC PLANS ON SITE FOR ALL FUTURE INSPECTIONS
2. INSTALL RECEPTACLES IN KITCHEN AND BATHROOM AS DISCUSSED
3. OK WALLS AND HARD LIDS APARTMENT AND OFFICE
04/23/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CANNOT USE EMT FOR SUPPORT OF LOW VOLTAGE CABLING
2. LOW VOLTAGE CABLE RUN THROUGH METAL STUDYING TO BE PROTECTED
3. MISSING SMOKE DETECTORS
4. MISSING RECEPTACLES
5. NEED REVISION FOR LIGHT FIXTURES ADDED TO APARTMENT
6. SEAL OPEN KNOCKOUTS
7. FINISH WIRING LIGHTS
8. PANELS NOT LOCATED PER PLAN
9. FAN BOXES TO BE LISTED FOR FAN USE/SUPPORT
10. SUPPORT/SECURE EMT WITHIN 3' OF BOXES