Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/02/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/24/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CHECK GROUNDING MAKE UP IN METER 2. BOND AROUND REDUCING WASHERS - NEC 250.98, 250.102 3. PLEASE HAVE METER REMOVED FOR NEXT INSPECTION 4. LABELING NOT PER APPROVED PLANS 5. INSTALL LOCKNUTS ON FITTINGS PROPERLY. TEETH TO DIG INTO METAL 6. CHECK SPLICES IN BELL BOXES ON ROOF 7. PROVIDE 6" OF FREE CONDUCTOR LENGTH IN BOXES PER NEC 300.14 8. CANNOT USE WHITE CONDUCTOR AS PHASE CONDUCTOR NEC 200.6 & 200.7 & 310.12 |