Permit: T07CM03940

Parcel: 141015560

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM03940

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/02/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/24/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CHECK GROUNDING MAKE UP IN METER
2. BOND AROUND REDUCING WASHERS - NEC 250.98, 250.102
3. PLEASE HAVE METER REMOVED FOR NEXT INSPECTION
4. LABELING NOT PER APPROVED PLANS
5. INSTALL LOCKNUTS ON FITTINGS PROPERLY. TEETH TO DIG INTO METAL
6. CHECK SPLICES IN BELL BOXES ON ROOF
7. PROVIDE 6" OF FREE CONDUCTOR LENGTH IN BOXES PER NEC 300.14
8. CANNOT USE WHITE CONDUCTOR AS PHASE CONDUCTOR
NEC 200.6 & 200.7 & 310.12